Williamsport Zoning Invalidity Resolution

City of Williamsport, Lycoming County

Williamsport City Council declared its 1998 zoning ordinance invalid for data centers on June 25, 2026, and the city now has a draft ordinance that would allow data centers only as a conditional use in one zoning district, with limits on noise, water use, height and generators.

Ordinance responseN/AN Central
At a glance

The project by the numbers

StatusOrdinance Response
First announced2026-06-25

Williamsport writes data center rules before any project arrives

The number that mattersThe draft would cap data center buildings at 45 feet and one story, require closed-loop cooling, and hold the day-night average noise level at the edge of any home, school or other sensitive property to 50 decibels.
Developer
No developer has applied. Councilman Jonah Milliken introduced the June resolution, which the assistant city solicitor helped write, and the city brought in engineering firm Barry Isett & Associates for zoning reviews while the draft ordinance was prepared.
Tenant
There's no project or tenant. City officials say no data center application exists in Williamsport.
Current stage
Council adopted Resolution 10088 on June 25 and Resolution 10091 on July 9, 2026, starting a 180-day curative amendment period. A public hearing draft of the data center amendment was posted September 29 and went to the city Planning Commission on October 5. Council still has to hold its hearing and vote, and its October 22 meeting was canceled.
Decision body
Williamsport City Council adopts the ordinance, after review by the Williamsport Planning Commission.
Top issues
Where data centers could go in the city, noise near homes, schools and other sensitive places, water use and the capacity of the city's water and sewer authorities, backup generator emissions, whether other electric customers could see higher costs, and who pays to tear a facility down.
Key opponents
No organized opposition group has been reported, and no one has publicly opposed the ordinance.
Key supporters
Council voted 6-0 on both resolutions. Councilman Jonah Milliken introduced the June resolution, Council President Eric Beiter signed it and Mayor Derek Slaughter approved it. Council member Yoder urged the city to use the state Department of Community and Economic Development's toolkit and other municipalities' ordinances as models.

How we got here

City Council voted 6-0 on June 25, 2026 to adopt Resolution 10088, declaring the city's 1998 zoning ordinance substantively invalid because it doesn't account for data centers or accessory uses including power generating facilities. The municipal curative amendment route starts a 180-day clock to write data center rules and blocks developer validity challenges while the work is underway. On July 9 council voted 6-0 for Resolution 10091, the required second resolution listing the specific defects. Lycoming County commissioners took the same step in June for the 19 municipalities in the county planning partnership, and Woodward and Pine Creek townships made similar moves. In July the county planning commission's chairman said Woodward and Washington townships and the City of Williamsport had ratified curative amendments setting data center conditions. In September the city brought in Barry Isett & Associates for zoning reviews, and a public hearing draft of the ordinance was posted September 29. The city Planning Commission took it up October 5.

What is at stake

Impacts raised and open questions

Noise and vibration

Medium

The draft sets a 24-hour community noise equivalent level of 50 dBA at the boundary of any property with a sensitive receptor such as a home, school or day care, and 70 dBA at other developed properties. Developers would need pre- and post-construction sound studies by a board-certified noise engineer, and low-frequency (C-weighted) noise must also be kept at acceptable levels.

City of Williamsport

Water

Medium

The draft requires closed-loop cooling, favors reclaimed water, and allows private wells or direct stream withdrawals only if the Williamsport Municipal Water Authority documents it can't meet the need. Applicants would need written sign-off on capacity from the water and sanitary authorities, a drought-response plan, and an annual report on water use.

City of Williamsport

Air quality

Medium

Backup generators would have to meet EPA Tier 4 emissions standards, test only on weekdays, and be counted and disclosed with fuel storage before approval. Applicants must identify all sources of fine particulates, volatile organic compounds and nitrogen oxides on the site.

City of Williamsport

Energy costs and the grid

Medium

Before approval, an applicant must show that the utility can serve it without raising usage fees or reducing service for existing customers, and any off-site grid upgrades must be paid for by the developer.

City of Williamsport

Visual and light

Low

Buildings would be limited to 45 feet and one story, set back at least 120 feet from property lines and 200 feet from sensitive receptors, with planted buffer yards of 100 to 300 feet along streets and near homes, depending on building footprint.

City of Williamsport
Timeline

How it has unfolded

  • 2026-06-18Lycoming County declares its zoning ordinance invalid for data centers and starts a curative amendment for its 19 partner municipalities. Williamsport Sun-Gazette
  • 2026-06-25Council votes 6-0 to declare the 1998 zoning ordinance substantively invalid as to data centers, starting the 180-day curative-amendment clock NorthcentralPA.com
  • 2026-07-09Council votes 6-0 for Resolution 10091, the second resolution setting out the specific findings of invalidity. City of Williamsport
  • 2026-09-08The Planning Commission hears that the city has contracted Barry Isett & Associates for zoning reviews and that a draft data center ordinance is coming in October. City of Williamsport Planning Commission
  • 2026-09-29The city posts a public hearing draft of the data center zoning amendment. City of Williamsport
  • 2026-10-05The Planning Commission takes up the data center zoning amendment as an action item. City of Williamsport Planning Commission
  • 2026-10-14The city cancels the October 22 City Council meeting. City of Williamsport
News

Coverage of this project

Sources

Know your rights

In Pennsylvania, the local zoning ordinance sets the route. A conditional use is decided by the elected governing body (supervisors, commissioners or council). A special exception or variance, and an appeal of a zoning officer’s decision, go to the Zoning Hearing Board. Each is a public hearing on a record: affected neighbors can ask for party status, cross-examine witnesses, and appeal. Municipalities can also adopt data center ordinances with enforceable standards.

Know your rights →

Take action

Organized community opposition is the single most effective check on these projects in Pennsylvania. Show up to hearings, submit comment when it is taken, support legal and expert-witness costs, and press your municipality for a real ordinance. Pennsylvania municipalities cannot simply freeze applications, but a curative amendment under the Planning Code gives them a defined window to fix a defective ordinance.

How communities push back →